TURBINE TRIP PROTECTIONS
There are the following turbine trip protections are given:-
- Channel-1
- Channel-2
- Channel-3
- Fire Protection (Channel-1 & Channel -2) from control desk & OWS Channel-1,Channel-2 & Channel-3. & MBLD 1 & 2 (from MOT room & TG floor)
- Condenser vacuum low trip 2/3 (2 out of 3 logic).
- Lubricating Oil pressure very low 2/3 (2 out of 3 logic).
- HP exhaust steam temperature. Very high 2/3 (2 out of 3 logic).
- Axial shift Very high 2/3 (2 out of 3 logic).
- HP Casing top bottom differential Temperature Very high (2 out of 2 logic) & load greater than 20% of rated load
- IP casing Front & Rear Top-bottom differential Temperature Very high (2 out of 2 logic) & load greater than 20% of rated load.
- Cold gas temperature after H2 cooler high (2 out of 3 logic).
- Seal oil temperature after cooler high (2 out of 3 logic).
- Liquid level in main leads high (2 out of 3 logic).
- Hot air temperature exciter high (2 out of 3 logic).
- Primary water temperature after cooler high (2 out of 3 logic).
- Stator water winding outlet flow low (2 out of 3 logic).
- Main bushing R flow low (2 out of 2 logic)
- Main bushing S flow low (2 out of 2 logic)
- Main bushing T flow low (2 out of 2 logic).
- Boiler trip to Turbine trip.
- Generator trip to Turbine trip
- MOT level very low (2 out of 3 logic) (Through Fire Protection logic)
FIRE PROTECTION
- Fire Protection
- Fire Protection – Channel-1 & channel -2 can be initiated from Push buttons on turbine desk.
- HMI panel.
- Push buttons in MOT room
- Push buttons at TG Floor
- MOT level very low
- If Fire Protection channel-1 or channel-2 acts, following operations take place
- Emergency trip of turbine.
- Oil system shutdown
- Control Fluid System shutdown
- Vacuum breaker opens if Generator breaker is close.
***